ASJSR

American Scholarly Journal for Scientific Research

ISSN: 3143-2999

Solar First, Storage Second: What a Year of Naperville Wastewater Plant Data Shows

By Lakhi Ananthula ·

Solar First, Storage Second: What a Year of Naperville Wastewater Plant Data Shows

Author: Lakhi Ananthula

In 2025, the solar array at Naperville’s Springbrook Water Reclamation Center supplied 9.56 percent of the plant’s electricity. In none of the year’s 8,760 hours did the array produce more than the plant was using, so there was never anything left over to store. The plant used electricity day and night, averaging 2.07 megawatts (MW). Even in the array’s best hour of the year, it produced 1.02 MWh while the plant used 2.08 MWh. When I added a battery charged only from leftover solar to the model, that 9.56 percent did not change.

I used 2025 solar generation and meter records provided by the City of Naperville to compare what the plant produced with what it used. The City identifies the existing array as 1 MW. I wanted to understand when a battery could increase the share supplied by solar.

What the data showed

The plant’s electricity use is recorded across two meters, so I summed both to calculate total demand. The City supplied 35,040 readings from each meter, taken every 15 minutes, and 8,760 hourly solar records. I grouped the meter readings into matching hourly totals to compare generation and demand.

Megawatts describe the rate of electricity use or generation. Megawatt hours (MWh) describe energy over time: a steady demand of 2 MW uses 2 MWh in one hour. I use MWh for plant energy, solar energy and battery capacity throughout the comparison.

Table 1. Measured electricity use and solar generation in 2025

Measure

2025 result

Annual plant electricity use

18,106.5 MWh

Annual solar generation

1,730.3 MWh

Average plant demand

2.07 MW

Annual demand covered by solar

9.56%

Hours with surplus solar

0 of 8,760

For example, a plant using 2 MWh in one hour can use all 0.6 MWh from its solar array and still need 1.4 MWh from the grid. If the array instead produces 2.5 MWh in that hour, 0.5 MWh is left to charge a battery. The amount stored depends on the battery’s available capacity, charging power and energy losses.

The U.S. Department of Energy’s guidance on solar and storage explains how batteries can make solar electricity available at a later time. Some energy is lost while charging and discharging, so the amount returned is smaller than the amount received.

What happened with more solar

To model increased solar generation, I scaled the existing hourly generation profile by factors of two and four while holding facility demand constant. These theoretical scenarios scale the baseline profile directly and do not account for physical or technical constraints such as inverter clipping, panel orientation, available space, or interconnection limits. Relative to the City’s reported 1 MW rating, these represent 2 MW and 4 MW scenarios. Doubling solar produced only 25 hours with a surplus, while four times the original solar produced 1,583. I compared the same 4 MWh battery across these scenarios to see how the amount of available solar affected storage.

Figure 1. Solar and demand across an average summer day

At the existing size, average solar output stays below average demand, even at noon. The measured 1× solar and demand curves show hourly means across 92 days from June through August 2025. Shading marks surplus in the modeled 4× scenario.

Coverage is the percentage of the plant’s annual electricity use supplied by solar, either directly or after storage.

Table 2. How solar expansion changes the value of storage

Solar scale

Surplus hours

Annual surplus (MWh)

Coverage: no battery

Coverage: 4 MWh battery

1× (existing)

0

0

9.56%

9.56%

2×

25

1.2

19.11%

19.11%

4×

1,583

1,620.4

29.28%

33.17%

At twice the original solar generation, the battery delivered only about 1.01 MWh during the year, so coverage with and without it rounded to 19.11 percent. At four times the solar generation, the battery delivered 704.9 MWh and raised coverage from 29.28 percent to 33.17 percent, an increase of 3.89 percentage points. Since battery capacity was the same, the difference came from how much surplus was available and when the plant could use it later.

For these calculations, I assumed that 85 percent of the energy sent into storage could be recovered after charging and discharging, following established modeling practices for round-trip efficiency in battery storage systems (e.g., Beck et al., 2016). The charging and discharging power limits match the system's capacity, and the operating rules restrict the battery to charging exclusively from surplus solar, utilizing up to 80 percent of its 4 MWh capacity (3.2 MWh usable), with each day beginning with no stored energy. I limited usable capacity to 80 percent to help protect battery life through controlled depth of discharge (e.g., Ecker et al., 2014), leaving 3.2 MWh in the 4 MWh battery. Each day began with no usable energy stored, keeping the comparison conservative by excluding energy carried over from previous days.

What this means for the plant

The 2025 results show that this plant would need more solar before a battery charged only from leftover solar could increase solar coverage. Charging a battery from the grid would serve a different purpose, which I did not model.

This study covers one year, so it cannot show how results would change with different weather or plant operations. System cost, battery aging, backup design and changes within each hour also remain outside the model. The larger solar and battery scenarios are simulations, not City construction plans.

Next, I would like to examine whether retired electric vehicle batteries could make that storage more affordable, a possibility discussed in a review by Dong and colleagues.

Thanks to the Naperville Electric Utility staff for sharing the data and helping me understand the records. The analysis and any errors are mine.

Data and References

L

Lakhi Ananthula

Lakhi Ananthula is a junior at Waubonsie Valley High School in Illinois, where she researches energy storage for renewable power systems.